Inverter Log - Powerware 9170 User Manual

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Operation

Inverter Log

The inverter (Battery mode) log is in menu 2, submenu 1. Move through
the menu structure by pressing the Menu button and pressing the
button to move down to menu 2. Press
press
The log stores up to 10 entries, in chronological order. You can use the
and
B
entry shows the date and time the unit switched to battery operation
(in 24-hour format), and the duration of battery operation (in hours and
minutes).
A typical entry might look like this:
In Figure 57, the most recent inverter log (2 1 1) is being displayed. If the
unit is still running on inverter (battery power), an asterisk (*) is
displayed beside the date. "09/29" is the date of the Battery mode
operation: September 29. "13:56" means that Battery mode operation
started at 1:56 p.m. And "01:04" means the batteries supplied power for
1 hour and 4 minutes.
Table 11 contains a description of all inverter messages.
Table 11. Inverter Log Messages
Message
Line Fault
Battery Test
Manual
82
again to view the most recent entry in the inverter log.
buttons to scroll up and down through the log entries. Each
Y
2 1 1
I
09/29 13:56 01:04
Line Fault
Slot
Top
Figure 57. Inverter Log Entry
Explanation
UPS switched to battery because the input voltage was too high or
too low.
Battery test initiated inverter operation.
Operator initiated inverter operation.
+
Powerware
9170
®
to move to submenu 1 and
#0
ESC
UPS User's Guide