Input Current Ratings - Powerware 9170 User Manual

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

UPS Electrical Installation

Input Current Ratings

Table 6 contains the required circuit breaker ratings for hardwired
installations. Circuit breaker ratings for units having an input line cord
are determined by the current capacity of the line cord.
Table 6. Required Input Circuit Breaker Sizes (200–240 Vac,
50/60 Hz)
NOTE
that user's guide (164201399) for the proper input circuit breaker sizes and
ratings.
NOTE
recommended that initial installation of the Powerware 9170
contain wiring to support the maximum capacity of the UPS cabinet:
3 kVA for 3-slot cabinets; 9 kVA for 6-slot cabinets; 18 kVA for 9- and
12-slot cabinets.
38
UPS Capacity
3 kVA
6 kVA
9 kVA
12 kVA
15 kVA
18 kVA
If you are installing an optional battery charger module, refer to
To accommodate the feature of easy system expandability, it is
+
Powerware
9170
UPS User's Guide
®
Input Circuit Breaker Rating
25A
40A
60A
80A
100A
125A
+
UPS
Rev B www.powerware.com