Stabilizer Bracket Installation (Twelve-Slot Cabinet Only) - Powerware 9170 User Manual

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Stabilizer Bracket Installation (Twelve-Slot Cabinet Only)

The 12-slot Powerware 9170
shipped with two stabilizer brackets. These brackets must be attached to
the wall or the floor behind the UPS cabinet. Under all module-loading
conditions, they act as a protective stop to prevent the cabinet from
falling forward if it is unintentionally pushed away from the wall.
Each bracket has holes that enable it to be attached by screws to either
the wall or the floor (or both) behind the intended cabinet installation
(see Figure 8). The stabilizer brackets are not attached to the cabinet
base itself.
Use the following steps to install the stabilizer brackets:
1.
2.
3.
4.
+
Powerware
9170
UPS User's Guide
®
+
UPS cabinet with non-isolated output is
Select the location for the brackets, approximately 12–16I
(30–41 cm) apart, at the floor/wall intersection behind the
intended cabinet location.
Using the proper type of customer-supplied screws for the
intended mounting surface, attach each bracket as shown in
Figure 8. All screws must be driven into structural material such
as wall studs.
Roll the UPS cabinet to its intended location. Position the rear
section of the cabinet base under the open ends of the
stabilizer brackets as far as the cabinet will go.
Turn all four caster bolts counter-clockwise until the cabinet
rests on the floor. Place a plastic cap into each bolt access hole.
Rev B www.powerware.com