Isolated Output Wiring Diagrams
In isolated-output systems, connect the neutral-to-ground
(neutral-to-earth) wire to the proper terminal before making any other
. A green and yellow neutral-to-ground bonding
connections to the UPS
wire is supplied, with one end connected to the ground (earth) UPS
terminal as shown in Figure 37. The other end of the wire (as shown by *
in Figure 37) must be attached to the proper output neutral terminal, as
specified in Figure 35 and Figure 36.
Ground terminations, inside the UPS rear panel, are located directly
below the line input terminals. Figure 17 on page 28 shows input and
+
output wiring terminals inside the Powerware 9170
UPS cabinet.
If there is any question as to the need for this bond wire, contact your
local regulatory agency or your service representative.
N-G Bond Wire
X1
X3
X0
X2
Figure 37. N-G Bond Wire
53
+
Powerware
9170
UPS User's Guide