Power Module Replacement - Powerware 9170 User Manual

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Maintenance

Power Module Replacement

The Powerware 9170
module easily without disconnecting the load or damaging the UPS.
NOTE
modules are insufficient to supply the required power. If empty slots exist,
install replacement modules before removing original ones.
Use care in removing and installing power modules. To remove a power
module:
1.
2.
3.
4.
5.
6.
7.
94
+
hot-swap feature allows you to replace a power
The UPS may switch to internal bypass if the remaining power
Remove the front cover panel.
The panels have spring latches on the left and right sides that
hold them in place.
Loosen the thumbscrew on the module handle. Press down on
the latch release at the center of the module handle and pull
the handle down.
As the module handle fully extends, the module disconnects.
Slide the module slowly out of the cabinet.
Use two hands to support the module. When fully extended,
lower the front down slightly and lift the rear edge over the
safety stop on the center support rail.
Treat the original and replacement modules with care to avoid
damaging connectors or internal circuitry. Label the original
module with masking tape or some other identifier. Record the
serial number of the replacement module for your warranty.
Insert the replacement module by sliding it carefully into the
cabinet. Lower the front down slightly and lift the rear edge
over the safety stop on the center support rail. Keep the
module handle extended until the module is fully inserted.
Raise the power module handle to secure the module into the
cabinet. Be sure the handle latch snaps into place. Tighten the
thumbscrew on the handle.
Reinstall the front cover panel.
+
Powerware
9170
UPS User's Guide
®
Rev B www.powerware.com
S

Advertisement

Table of Contents
loading

Table of Contents