Rack-Mount Installation (Three- And Six-Slot Cabinet) - Powerware 9170 User Manual

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Installation Setup
NOTE
need to place a thin steel plate under a corner.
bolts to level the cabinet.

Rack-Mount Installation (Three- and Six-Slot Cabinet)

NOTE
with the nine- and 12-slot rack-mount kit.
The 3- and 6-slot UPS cabinets may be installed in an EIA-standard 19I
(48.3-cm) equipment rack. An optional rack-mounting kit (ASY-0547),
containing brackets and required hardware, is available for such an
installation. For each 3-slot section, use the following mounting
procedure to convert the UPS cabinet and install it in the equipment
rack:
NOTE
two people to lift and position the cabinet into the equipment rack. Install
the cabinet in the rack before installing power and battery modules and
before making connections to the intended power source.
1.
2.
12
If the floor is uneven and the cabinet is tilted or unstable, you may
Stabilizer Bracket
Figure 8. Stabilizer Bracket Installation
For nine- and 12-slot cabinets, follow the installation instructions
The UPS cabinet is heavy (see page 102). This procedure requires
Remove the four screws (two on either side) securing the top
cover of the UPS cabinet. Carefully lift the cover straight up and
off to avoid stressing the front panel display. Set the cover
aside.
Remove the two cabinet side panels (4 panels in 6-slot cabinets)
by lifting the top edge. No other hardware must be detached.
Store or discard the side panels.
+
Powerware
9170
UPS User's Guide
®
Do not use the caster
Rev B www.powerware.com
S