Chapter 5

Isolated Output Wiring Diagrams

The wiring diagrams in this section are unique and specific to
installations in which the output of the Powerware 9170
galvanically isolated from the input.
Figure 35 and Figure 36 describe output wiring configurations for various
output voltages. Use Table 9 to identify the wiring diagrams and connect
the output AC wiring to the proper Powerware 9170
terminals. You must also set the operating menu parameter 4-2-4 for the
required output voltage as shown in the wiring configuration drawings.
NOTE
charger modules in the system.
NOTE
neutral-to-ground wire (N-G bond) to UPS output terminal as illustrated
in Figure 37 on page 53.
Table 9. Wiring Diagrams for Isolated Output (Split-Phase Power Modules Required)
UPS Input
UPS Input
UPS Output
UPS Output
Voltage
Voltage
100/200
100/200
110/220
110/220
115/230
115/230
115/230
115/230
120/240
120/240
120/208*
120/240
120/208*
120/208
120/208
120/208
127/220*
127/220
*External bypass switch, if installed, must be Break-Before-Make.
+
Powerware
9170
UPS User's Guide
®
Do NOT install more than seven power and/or optional battery
In isolated-output installations, connect the UPS green and yellow
External
External
Output Wires
Output Wires
Bypass
Yes
L1, L2, N
L1 L2 N
No
Yes
L1 L2 N
L1, L2, N
No
Rev B www.powerware.com
S
+
+
system power
Wiring Diagrams
Input
Output
Figure 18a on
Figure 35 on
page 29
page 52
Figure 18a on
Figure 35 on
page 29
page 52
Figure 18a on
Figure 36 on
page 29
page 52
Figure 18a on
Figure 36 on
page 29
page 52
UPS is
System
Figure 38 on
page 55
Figure 39 on
page 55
Figure 40 on
page 56
Figure 41 on
page 56
51