7.
NOTE
of the entire cabinet. Failure to balance the loads may cause an overload
alarm even if the full capacity of the UPS has not been reached.
NOTE
chassis without a power cord is 3-wire plus ground input. If you have a
Universal Power Module (ASY-0674), all receptacles MUST be re-wired
for a 2-wire plus ground input configuration as shown in Figure 20 on
page 30.
+
Powerware
9170
UPS User's Guide
®
Plug the equipment to be protected into the UPS output
receptacles. Turn on the equipment that is connected to the
UPS.
DO NOT protect laser printers with the UPS because of the
exceptionally high power requirements of the heating elements.
The total volt-ampere load must not exceed the volt-ampere rating
+
For Powerware 9170
UPS models with low-voltage output
receptacles, it is recommended to divide loads between upper
and lower receptacles as equally as possible. (In some
configurations, each set of receptacles is limited to one half of
the total UPS capacity.) Whether the cabinet has one panel
containing eight receptacles, two panels containing
16 receptacles, or three panels containing 24 receptacles, you
should try to supply half of the UPS output through the upper
half of the receptacles (X1) and the other half through the
lower half of the receptacles (X2), as shown in Figure 50.
X1
X2
Figure 50. Balancing Receptacle Loads
The factory-default wiring for all high-voltage receptacles in a
Rev B www.powerware.com
S
UPS Startup
X1
X2
67