Isolated Output Wiring Diagrams

Neutral-to-Ground Bonding for Isolated Output

As required under safety regulations issued by various regulatory
agencies, the UPS cabinet must have a ground-bond connection for the
neutral terminal of an isolated-output system. In such a system, the
customer must make the neutral-to-ground (also referred to as N-G or
neutral-to-earth) connection after selecting the desired output
configuration.
52
50 or 60 Hz
100/200, 110/220, 115/230, or 120/240V Out
with Isolated Output Option
Parameter 4-2-4 set to 200, 220, 230, or 240, as required.
X1
X3
X
100, 110,
115, or 120
200, 220, 230, or 240
L1
Figure 35. Isolated Outputs – Single-Phase Voltages
50 or 60 Hz
120/208 or 127/220V Out
with Isolated Output Option
Parameter 4-2-4 set to 208 or 220, as required.
X1
X3
X
L1
Figure 36. Isolated Outputs – Derived 3-Phase Voltages
+
Powerware
9170
®
X0
X2
X
X
N-G Bond
100, 110,
115, or 120
N
L2
X0
X2
X
X
N-G Bond
88 or 93
120 or 127
208 or 220
N
L2
UPS User's Guide