Chapter 3

3.1 Preliminary Installation Information

Refer to the following while installing the UPS system:

3.2 UPS Cabinet Installation

To install a UPS cabinet, perform the procedures in the following paragraphs.
Powerware
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
®

Installing the UPS System

Installation should be performed only by qualified personnel.
Appendix A for installation drawings and additional installation notes.
Dimensions are in millimeters and inches.
Do not tilt the cabinets more than
The conduit landing plates are to be removed to add conduit landing holes as required.
Plate material is 16 gauge steel (1.5 mm/0.06I thick).
The cabinets must be installed on a level floor suitable for computer or electronic
equipment.
If perforated floor tiles are required for ventilation, place them in front of the UPS. See
Table A on page A-3 for equipment weight and point loading.
Details about control wiring are provided in each procedure for connecting options and
features. Drawing 164201535-8 and Table T through Table Y starting on page A-33
identify the control wiring terminations.
NOTE
When a line-up–and–match UPS system is ordered together with battery
cabinets, the first battery cabinet is supplied with two cosmetic covers. The UPS cabinet,
additional battery cabinets, and other ancillary cabinets are supplied without cosmetic
covers.
NOTE
When a UPS system is ordered together with battery cabinets for standalone
installation, the first battery cabinet is supplied with two cosmetic covers. Additional
battery cabinets are supplied without cosmetic covers. Cosmetic covers must be ordered
for the UPS cabinet and/or other ancillary cabinets.
W A R N I N G
10° during installation.
3-1