Faulty Combination Of Pc Board - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.36 "PJ" Outdoor Unit:
Main PC Board or Faulty Combination of PC Board
PJ
Remote
Controller
Display
Applicable
RWEYQ60, 72, 84MTJU
Models
Method of
The faulty (or no) field setting after replacing main PC board or faulty PC board combination is
detected through communications with the inverter.
Malfunction
Detection
Malfunction
Whether or not the field setting or the type of the PC board is correct through the communication
date is judged.
Decision
Conditions
Supposed
Causes
Troubleshooting
206
Faulty Field Setting after Replacing
Faulty (or no) field setting after replacing main PC board
Mismatching of type of PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Has the PC
board been replaced?
YES
When replacing
the main PC board, were field
setting properly
made?
YES
Is the type of
PC board correct?
YES
∗Note) Type of PC board mismatching includes;
Main PC board
Inverter PC board (for compressor)
Fan driver PC board
NO
NO
NO
SiUS30-604
Correct the field
settings.
Replace with a correct
PC board.
Reset, and then restart.