Daikin VRV - WII Service Manual page 244

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

SiUS30-604
Troubleshooting
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Has a once
connected optional
controller for centralized
control been disconnected
or its address
changed?
NO
Is
the power supply
turned on for all optional
controllers for
centralized
control?
YES
Is
the reset switch
of all optional controllers
for centralized control set
to "normal"?
YES
Is
transmission wiring
disconnected or wired
incorrectly?
NO
Troubleshooting (OP: Central Remote Controller)
YES
NO
NO
YES
Reset power supply
simultaneously for all optional
controllers for centralized control.
Turn on power supply for all
optional controllers for centralized
control.
Set reset switch to "normal".
Fix the wiring correctly.
The PC board of one of the
optional controllers for centralized
control is defective. Try turning
on/off using each optional
controllers for centralized control,
and replace the PC board of the
one that is unable to control the
indoor unit.
(V2833)