Daikin VRV - WII Service Manual page 162

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

SiUS30-604
Malfunction
code
System
U0
U1
U2
U3
U4
U5
U5
U7
U8
U9
UA
UC
UE
UF
UH
Centralized
M1
Control
and
M8
Schedule
Timer
MA
MC
Heat
64
Reclaim
65
Ventilation
6A
6A
6F
6H
94
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Troubleshooting
Operation
Inspection
Unit No.
lamp
display
8
7
9
9
9
9
9
9
9
9
9
9
7
8
9
9
9
9
9
9
9
9
8
8
9
9
9
9
9
9
8 or 7
9
8 or 7
9
8 or 7
9
8 or 7
9
8
7
8
7
8
7
9
9
8
7
8
7
9
9
Malfunction contents
Low pressure drop due to refrigerant shortage or
9
electronic expansion valve failure
Reverse phase / open phase
9
Power supply insufficient or instantaneous failure
9
Check operation is not conducted.
9
Malfunction of transmission between indoor and outside
9
units
Malfunction of transmission between remote controller
9
and indoor unit
Failure of remote controller PC board or setting during
7
control by remote controller
Malfunction of transmission between outside units
9
Malfunction of transmission between master and slave
7
remote controllers (malfunction of slave remote
controller)
Malfunction of transmission between indoor unit and
9
outside unit in the same system
Excessive number of indoor units etc.
9
Address duplication of central remote controller
8
Malfunction of transmission between central remote
9
controller and indoor unit
Refrigerant system not set, incompatible wiring / piping
9
Malfunction of system, refrigerant system address
9
undefined
PC board defect
9
Malfunction of transmission between optional controllers
9
for centralized control
Improper combination of optional controllers for
9
centralized control
Address duplication, improper setting
9
Indoor unit's air thermistor error
9
Outside air thermistor error
9
Damper system alarm
9
Damper system + thermistor error
9
Malfunction of simple remote controller
9
Malfunction of door switch or connector
9
Internal transmission error
9
Troubleshooting by Remote Controller
Page
Referred
207
209
210
212
213
215
215
216
218
219
221
223
224
235
226
227
229
237
230
238
232
240
234
242
149