Field Setting
3.2
Field Setting from Outside Unit
3.2.1 Field Setting from Outside Unit
The following field settings are made by dip switches on PC board.
~DS1-4
Caution
DIP switch Setting after changing the main P.C.Board (A1P) to spare parts P.C.B.
When you change the main P.C.Board (A1P) to spare parts P.C.B., please carry out the following
setting.
DS No.
DS1-1
DS1-2 Domestic/Overseas
DS1-3
DS1-4
DS2-1 Domestic/Overseas
DS2-2 HP setting
DS2-3
DS2-4
110
Setting by dip switches
Dipswitch
No.
Setting
ON
DS1-1
OFF (Factory set)
ON
DS1-2
OFF (Factory set)
ON
DS2-1
~4
OFF (Factory set)
ON
DS3-1,
2
OFF (Factory set)
Item
—
setting
—
—
setting
(Horse power)
Setting item
Used to set cool/heat select by remote controller
Cool/Heat select
equipped with outside unit.
Not used
Do not change the factory settings.
Not used
Do not change the factory settings.
Not used
Do not change the factory settings.
ON
ON
OFF
OFF
1 2 3 4
1 2 3 4
DS1
DIP Switch Detail
ON
Domestic Japan 200V (Mainly for domestic Japan)
OFF Overseas
400V (Mainly for overseas)
ON
Overseas
OFF Domestic Japan
60, 72, 84
DS2-2
OFF
DS2-3
ON
DS2-4
OFF
Description
DS2
Contents
—
—
—
SiUS30-604
Test Operation