Troubleshooting by Indication on the Remote Controller
Troubleshooting
160
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn off the power supply.
Are there
foreign particles
around the fan?
NO
Are the
harness from the
fan motor and the harness
of A1P fan motor (fixed to
X20A) connected
properly?
YES
Can the
fan be removed
from the junction connector
between the fan motor and A1P
and rotated easily
with hands?
YES
Check the fan motor
connector. ∗
Does the
resistance between pins
satisfy the judgment
criteria?
YES
Are
heavy current PCB
(A1P) and low current PCB
(A2P) connected
properly?
YES
YES
NO
NO
∗Refer to the figure in following
page.
NO
NO
SiUS30-604
Remove the foreign particles.
Connect properly.
Replace the fan motor.
Replace the fan motor.
Connect properly.
Replace the indoor PCB.