Ue" Malfunction Of Transmission Between Centralized Controller And Indoor Unit - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.48 "UE"
Malfunction of Transmission between Centralized
Controller and Indoor Unit
UE
Remote
Controller
Display
Applicable
All models of indoor units
Centralized controller
Models
Method of
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
224
Malfunction of transmission between optional controllers for centralized control and indoor unit
Connector for setting master controller is disconnected.
Failure of PC board for central remote controller
Defect of indoor unit PC board
SiUS30-604
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents