Af" Indoor Unit: Drain Level Above Limit - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
"AF" Indoor Unit:
2.7
AF
Remote
Controller
Display
Applicable
FXFQ, FXSQ, FXMQ, FXDQ
Models
Method of
Water leakage is detected based on float switch ON/OFF operation while the compressor is in non-
operation.
Malfunction
Detection
Malfunction
When the float switch changes from ON to OFF while the compressor is in non-operation.
Decision
Conditions
Supposed
Causes
Troubleshooting
166
Drain Level above Limit
Humidifier unit (optional accessory) leaking
Defect of drain pipe (upward slope, etc.)
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Field drain
piping has a defect such as
upward sloping.
NO
A humidifier
unit (optional accessory)
is installed on the
indoor unit.
NO
YES
YES
SiUS30-604
Modify the drain piping.
Check if the humidifier unit is
leaking.
Defect of indoor unit PC board.
(V2782)
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents