Daikin VRV - WII Service Manual page 193

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
Discount the electronic expansion valve from the PC board and check the continuity between the
connector pins.
(Normal)
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
× : No continuity
180
1: Coil check method for the moving part of the electronic expansion valve
Pin No.
1. White
: Continuity
White (1)
Red (5)
Orange (3)
2. Yellow
3. Orange
×
Approx.
300Ω
×
(1) White
(2) Yellow
φ1
M
φ3
(3) Orange
(4) Blue
φ2
φ4
(5) Red
Yellow
Brown
Blue
(2)
(6)
(4)
(6) Brown
4. Blue
5. Red
×
Approx.
150Ω
×
Approx.
300Ω
×
Approx.
150Ω
×
SiUS30-604
6. Brown
×
Approx.
150Ω
×
Approx.
150Ω
×
Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents