Daikin VRV - WII Service Manual page 178

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

SiUS30-604
Discount the electronic expansion valve from the PC board and check the continuity between the
connector pins.
(Normal)
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
× : No continuity
Troubleshooting
1: Coil check method for the moving part of the electronic expansion valve
Pin No.
1. White
: Continuity
White (1)
Red (5)
Orange (3)
Troubleshooting by Indication on the Remote Controller
2. Yellow
3. Orange
×
Approx.
300Ω
×
(1) White
(2) Yellow
φ1
M
φ3
(3) Orange
(4) Blue
φ2
φ4
(5) Red
Yellow
Brown
Blue
(2)
(6)
(4)
(6) Brown
4. Blue
5. Red
×
Approx.
150Ω
×
Approx.
300Ω
×
Approx.
150Ω
×
6. Brown
×
Approx.
150Ω
×
Approx.
150Ω
×
165