U8" Malfunction Of Transmission Between Master And; Slave Remote Controllers - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.44 "U8"
Malfunction of Transmission between Master and

Slave Remote Controllers

U8
Remote
Controller
Display
Applicable
All models of indoor units
Models
Method of
In case of controlling with 2-remote controller, check the system using microcomputer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Detection
Malfunction
Normal transmission does not continue for specified period.
Decision
Conditions
Supposed
Causes
Troubleshooting
218
Malfunction of transmission between main and sub remote controller
Connection between sub remote controllers
Defect of remote controller PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Using 2-remote
controllers control.
YES
SS1
of both remote controllers is
set to "SUB".
YES
SS1
NO
of remote controller PC boards
is set to "MAIN".
YES
NO
SiUS30-604
NO
Set SS1 to "MAIN"; the
power supply off once and
then back on.
Turn the power off and then
back on. If a malfunction
occurs, replace the remote
controller PC board.
Set one remote controller to
"MAIN"; the power supply off
once and then back on.
(V2825)