SiUS30-604
Model Name (Combination Unit)
Model Name (Combination Unit)
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Heat Exchanger
Type
Piston Displacement
Number of Revolutions
Comp.
Motor Output×Number
of Units
Starting Method
Liquid Pipe
Suction Gas Pipe
Discharge Gas Pipe
Connecting
Pipes
Water inlet
Water outlet
Drain outlet
Machine Weight (Mass)
Safety Devices
Capacity Control
Refrigerant Name
Refrigerant
Charge
Control
Refrigerator Oil
Standard Accessories
Drawing No.
Notes:
1.
2. This unit cannot be installed outdoors.
3. Hold ambient condition at 35~95°F, ~80%RH
4. There are some cases where capacity decreases depending on operating states.
Specifications
Btu / h
Btu / h
in
m³/h
r.p.m
kW
in
in
in
Lbs
%
Lbs
Installation Manual, Operation Manual, Connection Pipes, Clamps, Strainer, Conduit Mounting Plate
1 Indoor temp. : 80°FDB, 67°FWB / inlet water temp. : 85°F / outlet water temp. : 95°F
Equivalent piping length : 25ft, level difference : 0ft.
2 Indoor temp. : 70°FDB, 60°FWB / inlet water temp. : 70°F / Equivalent piping length : 25ft, level difference : 0ft.
3 In the case of heat pump system, suction gas pipe is not used.
4 In the case of heat recovery system.
5 In the case of heat pump system.
Install indoors (Machine room etc.).
Heat rejection from the casing : 0.64kW×3
RWEYQ216MTJU
RWEYQ72MTJU+RWEYQ72MTJU+RWEYQ72MTJU
216,000
243,000
Ivory White (5Y7.5/1)
(39-3/8×30-3/4×21-11/16)×3
Stainless Steel Plate Type
Hermetically Sealed Scroll Type
11.18×3
5,280×3
3.6×3
Soft Start
5/8 in C1220T (Flare Connection) -Main Line-
1-3/8 in C1220T (Brazing Connection)
4 1-1/8 in C1220T,
5 1-3/8 in C1220T (Brazing Connection) -Main Line-
1 1/4 FPT Female Thread
1 1/4 FPT Female Thread
1/2 FPS Female Thread
330+330+330
High Pressure Switch, Inverter Overload Protector, Fusible Plugs
8~100
R-410A
9.9+9.9+9.9
Electronic Expansion Valve
Synthetic (Ether) Oil
4D054575D
Specifications
3 -Main Line-
21