SiUS30-604
2.37 "UO"
Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure
U0
Remote
Controller
Display
Applicable
RWEYQ60, 72, 84MTJU
Models
Method of
Detect insufficient gas using low pressure or difference in temperature between the suction pipe
and the heat exchanger.
Malfunction
Detection
Malfunction
In cooling
Decision
In heating
Conditions
∗
Supposed
Causes
Troubleshooting
Low pressure of 36.2psi or less continues for 30 minutes
Suction gas superheated degree of 36°F or more continues for 60 minutes.
Abnormality is not confirmed and operation is continued.
Insufficient gas or clogged refrigerant (wrong piping)
Faulty thermistor (R2T, R4T)
Faulty low pressure sensor
Faulty main PCB (A1P)
Troubleshooting by Indication on the Remote Controller
207