Daikin VRV - WII Service Manual page 40

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

SiUS30-604
Slim Ceiling Mounted Duct Type
Model
1 Cooling Capacity
2 Heating Capacity
Casing / Color
Dimensions: (H×W×D)
Rows×Stages×FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output
Fan
Air Flow Rate (H/L)
External Static Pressure
4
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
5 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
Specifications
Btu/h
Btu/h
in
7-7/8 × 35-7/16 × 24-7/16
ft²
HP
cfm
Pa
Microprocessor Thermostat for Cooling and Heating
Removal, Washable, Mildew Proof
in
in
in
(External Dia. 1-1/32 Internal Dia. 25/32)
Lbs
dBA
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Screws, Washers, Conduit Mounting
Plate, Insulation Tube.
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
|Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure means
" High static pressure – Standard ".
5 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
FXDQ18MVJU
18,000
20,000
Galvanized Steel Plate
3 × 12 × 17
1.89
Sirocco Fan
0.17
440/350 (H/L)
44-15
Direct Drive
Foamed Polyethylene
φ
1/4 (Flare Connection)
φ
1/2 (Flare Connection)
VP20
63
35/31
R-410A Series
FXDQ24MVJU
24,000
27,000
Galvanized Steel Plate
7-7/8 × 43-5/16 × 24-7/16
3 × 12 × 17
Sirocco Fan
580/460 (H/L)
44-15
Direct Drive
Microprocessor Thermostat for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ
3/8 (Flare Connection)
φ
5/8 (Flare Connection)
VP20
(External Dia. 1-1/32 Internal Dia. 25/32)
36/32
Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Screws, Washers, Conduit Mounting
Plate, Insulation Tube.
C:3D051780A
Specifications
2.44
0.17
71
27

Hide quick links:

Advertisement

Table of Contents
loading