Troubleshooting (OP: Schedule Timer)
"MA"
4.4
Improper Combination of Optional Controllers for
Centralized Control
MA
Remote
Controller
Display
Applicable
Schedule timer
Models
Method of
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Detection
Malfunction
When the schedule timer is set to individual use mode, other central component is present.
When multiple master controller are present.
Decision
Conditions
Supposed
Causes
240
Improper combination of optional controllers for centralized control
More than one master controller is connected.
Defect of PC board of optional controller for centralized control
SiUS30-604
Troubleshooting