21.1.9 Indoor unit field setting

RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P749918-1 – 2023.12
[2‑81]
0
1 (default)
2
3
For more information and advice about the impact of these settings, see
"21.2 Energy saving and optimum
[2‑82]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].
[2‑82]
0
1 (default)
2
3
For more information and advice about the impact of these settings, see
"21.2 Energy saving and optimum
[2‑88]
Automatic leak detection activation.
When you want to use the automatic leak detection function you have to activate
this setting. By activating setting [2‑88], the automatic leak detection will be
executed depending on the defined value setting. The timing for the next
automatic refrigerant leak detection is subject to setting [2‑65]. The automatic leak
detection will be executed in [2‑65] days.
Each time when the automatic leak detection function was executed the system
will stay idle until it is restarted by manual thermo ON request or by next
scheduled action.
[2‑88]
0 (default)
1
2
15(25)-13
Safety system deactivation.
When the room where the indoor unit is installed is big enough that no safety
measure is required, the R32 leak safety system in that indoor unit can be
deactivated by this setting.
st
Setting
1
code
15/25
13
Cooling comfort setting
Eco
Mild
Quick
Powerful
operation" [
4
 156].
Heating comfort setting
Eco
Mild
Quick
Powerful
4
operation" [
 156].
Description
No leak detection planned.
Leak detection planned once in [2‑65] days.
Leak detection planned every [2‑65] days.
Safety system deactivation
Function
R32 leak safety
system setting
21
Configuration
|
nd
2
code
Description
01
Disabled
02
Enabled
Installer and user reference guide
155