xii
®
UL
Cautions, Warnings, and Instructions
Wiring Warnings
for Electrical
Practices and
Wire Sizes
The Cautions, Warnings, and instructions in this section summarize the procedures necessary to
ensure an inverter installation complies with Underwriters Laboratories
The SJ700
series inverter family is an open-type and/or Enclosed Type 1 (when employing
2
accessory Type 1 Chassis Kit) AC inverter with 3-phase input and 3-phase output. The inverter
are intended for use in an enclosure. The inverter supplies adjustable voltage and adjustable
frequency to an AC motor. The inverter can automatically maintain a constant volts/Hz ratio to
enhance the motor capability throughout its entire speed range.
WARNING: Use 65/75°C Cu wire only or equivalent. For SJ700 series except SJ700-300Lxx
and SJ700-370Lxx.
WARNING: Use 75°C Cu wire only or equivalent. For SJ700-300Lxx and SJ700-370Lxx.
WARNING: Suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes with 240 V maximum. For models with suffix L (200V class).
WARNING: Suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes with 480 V maximum. For models with suffix H (400V class).
WARNING: The inverter must be installed in an environment that is rated for at least Pollution
Degree 2 or equivalent.
WARNING: The ambient temperature must not exceed 50°C.
WARNING: The capacitor discharge time is 10 minutes or more. (Caution: Care must be taken
to avoid the risk of electric shock.)
WARNING: Each model of the inverter has a solid-state overload protection circuit or an
equivalent feature for the motor.
®
guidelines.