Chapter 2 Installation and Wiring
R
S
(L1)
(L2)
G
Jumper connecting
Terminals PD and P
When not using the DCL,
do not remove the jumper
from terminals PD and P.
[Method of enabling/disabling the EMC filter function]
Enabling the EMC filter
Reference: Leakage current by inverter with model EMC filter enabled or disabled (reference data)
The table below lists the reference currents that may leak from the inverter when the internal EMC filter is enabled or disabled.
(Leakage current is in proportion to the voltage and frequency of input power.)
Note that the values listed in the table below indicate the reference currents leaking from the inverter alone. The values exclude
current leakage from external devices and equipment (e.g., power cables).
Internal EMC filter enabled
Internal EMC filter disabled
Terminal layout
charge lump
T
PD
P
(L3)
(+1)
(+)
200 V class model (input power: 200 VAC, 50 Hz) 400 V class model (input power: 400 VAC, 50 Hz)
5.5kW~11kW
15kW~37kW
Ca 48mA
Ca 23mA
Ca.0.1mA
Ca.0.1mA
R0
T0
N
U
V
(-)
(T1)
(T2)
Ground terminal with
jumper (shaded in the
figure) to enable/disable the
EMC filter function
Disabling the EMC filter (factory setting)
45kW~55kW
5.5kW~11kW
Ca 23mA
Ca.95mA
Ca.0.1mA
Ca.0.2mA
2 - 18
Inverter model
G
W
(T3)
G
SJ700-550LFF2
R0 and T0: M4
Ground terminal:
M8
Other terminals:
M10
15kW~37kW
45kW~55kW
Ca.56mA
Ca.56mA
Ca.0.2mA
Ca.0.2mA