(viii) 07 command: This command writes data to a specified setting item in the inverter.
- Transmission frame
Frame format
STX
Station No. Command Parameter
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
Command
Command to be transmitted
Parameter
Data parameter number
Parameter data (decimal ASCII
Data
code)
BCC
Block check code
CR
Control code (Carriage Return)
Note 14: Possible range of parameters is as follows.
F002-, A001-, b001-, C001-, H001-, P001- (F001 is written with 01 command.)
- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.
(ix) 08 command: This command initializes specified settings in the inverter.
The setting items to be initialized follow the setting of the initialization mode (b084). When "b084" is "00",
the trip history data is cleared.
- Transmission frame
Frame format
STX
Station No. Command
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
Command
Command to be transmitted
BCC
Block check code
CR
Control code (Carriage Return)
- Response frame
Positive response: See Item (2)-(i) of this section.
Negative response: See Item (2)-(ii) of this section.
Description
BCC
Description
Chapter 4 Explanation of Functions
Data
BCC
Data size
1 byte
STX (0x02)
2 bytes
01 to 32, or FF (broadcast to all stations)
2 bytes
07
4 bytes
See Note 14.
8 bytes
See Note 13.
XOR of the items from "Station No." to "Data."
2 bytes
See Item (3) of this section.
1 byte
CR (0x0D)
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32, or FF (broadcast to all stations)
2 bytes
08
XOR of the items from "Station No." to "Data."
2 bytes
See Item (3) of this section.
1 byte
CR (0x0D)
4 - 127
CR
Setting
Setting