Hitachi SJ700-2 Instruction Manual page 124

Sj700-2 series
Hide thumbs Also See for SJ700-2:
Table of Contents

Advertisement

Data
Description
53
MJA: Major failure
54
WCO
55
WCOI
56
WCO
4.2.59 Intelligent output terminal a/b (NO/NC) selection
The intelligent output terminal a/b (NO/NC) selection function
allows you to specify a-contact or b-contact output for each of
the intelligent output terminals [11] to [15] and the alarm relay
terminal.
The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal
is used for relay output.
Item
Terminal active state
Alarm relay active state
- An a-contact turns on the output signal when closed and turns it off when opened.
- A b-contact turns on the output signal when opened and turns it off when closed.
(1) Specifications of intelligent output terminals [11] to [15]
Intelligent output terminals [11] to [15] have the following specifications:
Inside the
inverter
Setting of C031 to C035
00
(a-contact)
01
(b-contact)
(2) Specifications of alarm relay terminal
The alarm relay terminal uses a normally-closed (NC) contact that operates as described below.
Inside the
inverter
Example of operation as an alarm output terminal
Setting
Power
Inverter
of C036
supply
status
Error
ON
00
Normal
OFF
Error
ON
01
Normal
(default)
OFF
Major failure signal
Window comparators function
Function code
C031 to C035
C036
15 CM2 ...
...
Power supply
Output signal
ON
ON
OFF
OFF
ON
ON
OFF
OFF
AL0 AL1 AL2
Output terminal state
AL1-AL0
AL2-AL0
Closed
Open
Open
Closed
Open
Closed
Open
Closed
Closed
Open
Open
Closed
Chapter 4 Explanation of Functions
Reference item
C031 to C035: Terminal [11] to [15] active state
C036: Alarm relay active state
Data
00
01
00
01
11
(Between each terminal and CM2)
Voltage drop when turned on: 4 V or less
Allowable maximum voltage: 27 VDC
Allowable maximum current: 50 mA
Maximum contact
capacity
AL1-AL0
Minimum contact
capacity
Maximum contact
capacity
AL2-AL0
Minimum contact
capacity
4 - 61
Related code
Description
a-contact (NO)
b-contact (NC)
a-contact (NO)
b-contact (NC)
Electric characteristics
Resistance load
Inductive load
250 VAC, 2 A
250 VAC, 2 A
30 VDC,
3
A
30 VDC, 8 A
100 V AC, 10 mA
5 VDC, 100 mA
250 VAC, 1A
250 VAC, 0.2 A
30 VDC, 1A
30 VDC, 0.2 A
100 VAC, 10 mA
5 VDC, 100 mA
Page
4-70
4-71

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents