Chapter 8 List of Data Settings
Code
Function name
Cumulative input power data
b078
clearance
Cumulative input power display
b079
gain setting
b082
Start frequency adjustment
b083
Carrier frequency setting
Initialization mode (parameters or
b084
trip history)
b085
Country code for initialization
Frequency scaling conversion
b086
factor
b087
STOP key enable
b088
Restart mode after FRS
Automatic carrier frequency
b089
reduction
b090
Dynamic braking usage ratio
b091
Stop mode selection
b092
Cooling fan control
b095
Dynamic braking control
b096
Dynamic braking activation level
Thermistor for thermal protection
b098
control
b099
Thermal protection level setting
b100
Free-setting V/f frequency (1)
b101
Free-setting V/f voltage (1)
b102
Free-setting V/f frequency (2)
b103
Free-setting V/f voltage (2)
b104
Free-setting V/f frequency (3)
b105
Free-setting V/f voltage (3)
b106
Free-setting V/f frequency (4)
b107
Free-setting V/f voltage (4)
b108
Free-setting V/f frequency (5)
b109
Free-setting V/f voltage (5)
b110
Free-setting V/f frequency (6)
b111
Free-setting V/f voltage (6)
b112
Free-setting V/f frequency (7)
b113
Free-setting V/f voltage (7)
b120
Brake Control Enable
b121
Brake Wait Time for Release
b122
Brake Wait Time for Acceleration
b123
Brake Wait Time for Stopping
b124
Brake Wait Time for Confirmation
b125
Brake Release Frequency Setting
b126
Brake Release Current Setting
b127
Braking frequency
b130
Overvoltage suppression enable
b131
Overvoltage suppression level
Acceleration and deceleration
b132
rate at overvoltage suppression
Overvoltage suppression
b133
propotional gain
Overvoltage suppression Integral
b134
time
Monitored data or setting
Clearance by setting "01" and pressing the STR key
1. to 1000.
0.10 to 9.99 (Hz)
0.5 to 15.0 (kHz) (subject to derating)
00 (clearing the trip history), 01 (initializing the data),
02 (clearing the trip history and initializing the data)
00 (Japan), 01 (EU), 02 (U.S.A.)
0.1 to 99.0
00 (enabling), 01 (disabling), 02 (disabling only the function to stop)
00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (starting
with active matching frequency)
00: invalid, 01: valid
0.0 to 100.0 (%)
00 (deceleration until stop), 01 (free-run stop)
00 (always operating the fan), 01 (operating the fan only during inverter
operation [including 5 minutes after power-on and power-off])
00 (disabling), 01 (enabling [disabling while the motor is topped]), 02
(enabling [enabling also while the motor is topped])
330 to 380, 660 to 760(V)
00 (disabling the thermistor), 01 (enabling the thermistor with PTC), 02
(enabling the thermistor with NTC)
0. to 9999. (Ω)
0. to "free-setting V/f frequency (2)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (3)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (4)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (5)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (6)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (7)" (Hz)
0.0 to 800.0 (V)
0. to "free-setting V/f frequency (8)" (Hz)
0.0 to 800.0 (V)
00 (disabling), 01 (enabling)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.0 to 2.00 x "rated current"
0.00 to 99.99, 100.0 to 400.0 (Hz)
00 (disabling the restraint), 01 (controlled deceleration), 02 (enabling
acceleration)
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
0.10 to 30.00 (s)
0.00 to 2.55
0.000 to 9.999 / 10.00 to 65.53 (s)
8 - 8
Setting during
Default
operation
(allowed or
not)
_FF
_FEF
_FUF
00
1.
0.50
5.0
00
00
01
02
1.0
00
00
00
0.0
00
00
00
360/
720
00
3000.
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
0.
0.0
00
0.00
0.00
0.00
0.00
0.00
Rated current of inverter
0.00
00
380/
760
1.00
0.50
0.060
Change
during
operation
Page
(allowed or
not)
4-4
4-42
4-43
4-75
4-2
4-9
4-52
4-44
4-45
4-9
4-45
4-72
4-17
4-81
4-41