4.2.29 Electronic thermal protection
The electronic thermal protection function allows you to protect
the motor against overheating. Make settings of this function
based on the rated current of the motor. The inverter will trip for
overheat protection according to the settings.
This function provides optimum overheat protection that is also
designed with the lowering of the motor's cooling performance
at low speeds in mind.
You can configure this function so that the inverter outputs a
warning signal before it trips for electronic thermal protection.
(1) Electronic thermal level
Item
Electronic thermal
setting (calculated within
the inverter from current
output)
(Example) Setting on the SJ700-150LFF
Rated current: 64 A
Range of setting: 12.8 A (20%) to 64.0 A (100%)
When 64 A is set as the electronic thermal setting (b012),
the time-limit characteristic is as shown on the right.
(2) Electronic thermal characteristic
The frequency characteristic set as the electronic thermal characteristic is integrated with the value of
"b012", "b212", or "b312".
The cooling-fan performance of a general-purpose motor lowers when the motor speed is low. So load
(current) is decreased.
The reduced-torque characteristic is designed to match the heat generation by Hitachi's general-purpose
motors.
Item
Electronic thermal
characteristic
(a) Reduced-torque characteristic
The time-limit characteristic determined by the value of "b012", "b212", or "b312" is integrated with each
frequency multiplied by reduction scales.
Reduction
scale
X1.0
X0.8
X0.6
0
5
16
0
6
20
Function code
"0.2 x rated current" to
b012/b212/b312
"1.0 x rated current"
Function code
b013/b213/b313
Inverter output
frequency (Hz)
50
60
Base frequency
Chapter 4 Explanation of Functions
b012/b212/b312: Electronic thermal setting
(calculated within the inverter from current output),
1st/2nd/3rd motors
b013/b213/b313: Electronic thermal characteristic,
1st/2nd/3rd motors
b015/b017/b019: Free setting, electronic thermal
frequency (1) (2) (3)
b016/b018/b020: Free setting, electronic thermal
current (1) (2) (3)
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C061: Electronic thermal warning level setting
Range of data
See the example below.
Trip time (s)
60
3.0
0
Data
00
Reduced-torque characteristic
01
Constant-torque characteristic
02
Free setting of electronic thermal characteristic
Example) Setting on the SJ700-150LFF (rated current: 64 A)
When "b012" is 64 A, the base frequency is 60 Hz,
and output frequency is 20 Hz:
Trip time (s)
60
3.0
0
(87.2%)
4 - 37
Related code
Description
Motor current (A)
69.8
96
128
(Ratio to the rated
(109%)
(150%)
(200%)
current of inverter)
Description
Motor current (A)
55.8
76.8
102.4
(Ratio to the rated
(120%)
(160%)
current of inverter)