Hitachi SJ700-2 Instruction Manual page 29

Sj700-2 series
Hide thumbs Also See for SJ700-2:
Table of Contents

Advertisement

(1) Explanation of main circuit terminals
Symbol
Terminal name
R, S, T
Main power input
(L1, L2, L3)
U, V, W
Inverter output
(T1, T2, T3)
PD, P
DC reactor connection
(+1, +)
P, RB
External braking
(+, RB)
resistor connection
P, N
Regenerative braking
(+, -)
unit connection
G
Inverter ground
(2) Explanation of control circuit terminals
Symbol
Terminal name
Analog power
L
(common)
Frequency
H
setting power
Frequency
O
O2
Frequency
OI
Analog monitor
AM
Analog monitor
AMI
Digital monitor
FM
Interface power
P24
Interface power
CM1
(common)
Forward rotation
FW
1
2
3
4
Intelligent input
5
6
7
8
Connect to the AC power supply.
Leave these terminals unconnected when using a regenerative converter (HS900 series).
Connect a 3-phase motor.
Remove the jumper from terminals PD and P, and connect the optional power factor reactor
(DCL).
Connect the optional external braking resistor.
(The RB terminal is provided on models with 22 kW or less capacity.)
Connect the optional regenerative braking unit (BRD).
Connect to ground for grounding the inverter chassis by type-D grounding (for 200 V class
models) or type-C grounding (for 400 V class models).
This common terminal supplies power to frequency command terminals (O,
supply
O2, and OI) and analog output terminals (AM and AMI). Do not ground this
terminal.
This terminal supplies 10 VDC power to the O, O2, OI terminals.
supply
Input a voltage (0 to 10 VDC) as a frequency command. 10 V specifies the
maximum frequency.
command
To specify the maximum frequency with a voltage of 10 V or less, set the
(voltage)
voltage using function "A014".
Auxiliary
Input a voltage (0 to ±10 VDC) as a signal to be added to the frequency
frequency
command input from the O or OI terminal. You can input an independent
command
frequency command from this terminal (O2 terminal) alone by changing the
(voltage)
setting.
Input a current (4 to 20 mA DC) as a frequency command. 20 mA specifies
the maximum frequency.
command
The OI signal is valid only when the AT signal is on. Assign the AT function
(current)
to an intelligent input terminal.
This terminal outputs one of the selected "0 to 10 VDC voltage output"
monitoring items. The monitoring items available for selection include
output frequency, output current, output torque (signed or unsigned),
(voltage)
output voltage, input power, electronic thermal overload, LAD frequency,
motor temperature, heat sink temperature, and general output.
This terminal outputs one of the selected "4 to 20 mA DC current output"
monitoring items. The monitoring items available for selection include
output frequency, output current, output torque (unsigned), output voltage,
(current)
input power, electronic thermal overload, LAD frequency, motor
temperature, heat sink temperature, and general output.
This terminal outputs one of the selected "0 to 10 VDC voltage output
(PWM output mode)" monitoring items. The monitoring items available for
selection include output frequency, output current, output torque
(unsigned), output voltage, input power, electronic thermal overload, LAD
(voltage)
frequency, motor temperature, heat sink temperature, general output,
digital output frequency, and digital current monitor.
For the items "digital output frequency" and "digital current monitor," this
terminal outputs a digital pulse signal at 0/10 VDC with a duty ratio of 50%.
This terminal supplies 24 VDC power for contact input signals.
If the source logic is selected, this terminal is used as a common contact
supply
input terminal.
This common terminal supplies power to the interface power supply (P24),
thermistor input (TH), and digital monitor (FM) terminals. If the sink logic is
supply
selected, this terminal is used as a common contact input terminal. Do not
ground this terminal.
Turn on this FW signal to start the forward rotation of the motor; turn it off to
command
stop forward rotation after deceleration.
Select eight of a total 60 functions, and assign these eight functions to
terminals 1 to 8.
Note:
If the emergency stop function is used, terminals 1 and 3 are used
exclusively for the function. For details, see Item (3), "Emergency stop
function" (on page 2-8).
Chapter 2 Installation and Wiring
Description
Description
2 - 7
Electric property
Allowable load current: 20
mA or less
Input impedance: 10kΩ
Allowable input voltages:
-0.3 to +12 VDC
Input impedance: 10kΩ
Allowable input voltages:
0 to ±12 VDC
Input impedance: 10kΩ
Maximum
allowable
current: 24 mA
Maximum
allowable
current: 2 mA
Allowable load impedance:
250Ω or less
Maximum
allowable
current: 1.2 mA
Maximum frequency: 3.6
kHz
Maximum allowable output
current: 100 mA
[Conditions
for
turning
contact input on]
Voltage across input and
PLC: 18 VDC or more
Input impedance between
input and PLC: 4.7kΩ
Maximum allowable voltage
across input and PLC: 27
VDC
Load current with 27 VDC
power: about 5.6 mA