Hitachi SJ700-2 Instruction Manual page 189

Sj700-2 series
Hide thumbs Also See for SJ700-2:
Table of Contents

Advertisement

(vii) 06 command: This command reads a specified setting item from the inverter.
- Transmission frame
Frame format
STX
Station No. Command Parameter
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
Command
Command to be transmitted
Parameter
Data parameter number
BCC
Block check code
CR
Control code (Carriage Return)
Note 12: The parameters that can be specified for reading are F002 to F004, A001 to A153, b001 to
b132, C001 to C159, H003 to H073, and P001 to P131. (To read the F001 parameter, use the
01 command.)
- Response frame
Positive response:
Frame format
STX
Station No.
STX
Control code (Start of TeXt)
Station number of control-target
Station No.
inverter
ACK
Control code (acknowledgement)
Data to be sent (decimal ASCII
Data
code)
BCC
Block check code
CR
Control code (Carriage Return)
Note 13: When the read parameter is an selection item, the Data part contains the code data
corresponding to the selection.
The code data corresponding to "H003" or "H203" (motor capacity selection) is as follows:
Code data
Japan or U.S.A. mode
(b085 = 00 or 02)
EU mode (b085 = 01)
Code data
Japan or U.S.A. mode
(b085 = 00 or 02)
EU mode (b085 = 01)
For the value contained in the Data part when the read parameter is a numerical item, see the list of
function codes.
(Example) When the setting of the acceleration (1) time (F002) is 30.00 seconds, the Data part contains
"3000".
Negative response: See Item (2)-(ii) of this section.
Description
ACK
Data
Description
00
01
0.2 kW
0.4
-
0.2 kW
0.37
11
12
5.5 kW
7.5
5.5 kW
7.5
Chapter 4 Explanation of Functions
BCC
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32
2 bytes
06
4 bytes
See Note 12.
XOR of the items from "Station No." to "Data."
2 bytes
See Item (3) of this section.
1 byte
CR (0x0D)
BCC
CR
Data size
1 byte
STX (0x02)
2 bytes
01 to 32
1 byte
ACK (0x06)
8 bytes
See Note 13.
XOR of the items from "Station No." to "Data."
2 bytes
See Item (3) of this section.
1 byte
CR (0x0D)
02
03
04
05
0.75
-
-
0.55
0.75
1.1
-
13
14
15
16
11
15
18.5
22
11
15
18.5
22
4 - 126
Setting
Setting
06
07
08
09
1.5
2.2
3.7
-
1.5
2.2
3.0
-
17
18
19
20
30
37
45
55
30
37
45
55
10
-
4.0
21
75
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents