Figure 5-22, Tfmr Overtemp Fault

Tfmr Overtemp - This fault message is displayed when the TCO
(Temperature Cut-Out) opens and causes the inverter to shutdown to protect
the internal power transformer from damage. When the TCO has cooled
down, the inverter will automatically restart and resume operation.
Remedy: If the fault occurs while inverting, reduce the load on the
inverter; if it occurs while charging, turn down the charge rate. If
this fault occurs often, ensure the inverter is in a cool location, has
adequate ventilation and the internal cooling fans are operational.
5.3.3.2 Remote Fault Message – The remote control may not be functioning
correctly and can also display a fault condition. Refer to the following fault
message to help troubleshoot the remote.
PWR
Fatal Error $
FAULT
Settings/Info...
CHG
INV

Figure 5-23, Fatal Error $ Fault

Fatal Error $ - This fault message indicates that the remote's internal
data addressing was unrecognizable; similar to a computer lock-up.
Remedy: Reset the remote by disconnecting the remote commu-
nications cable from the inverter for 5 seconds and then reconnect
(see figure 2-2). If the fault continues after resetting the remote,
the remote requires service at an authorized service facility.
Info: The bottom line may not display correct information while the
Fatal Error $ fault condition is displayed; ignore any remote display
information during a Fatal Error $ fault.
PWR
No Inverter Comm
FAULT
Settings/Info...
CHG
INV

Figure 5-24, No Inverter Comm

No Inverter Comm - This fault message indicates that the remote is no
longer receiving any communication data via the Magnum Network.
Remedy: Reset the remote by disconnecting the remote communica-
tions cable from the inverter for 5 seconds and then reconnect (see
figure 2-2). If the fault continues, check/replace the remote cable.
©2009 Magnum Energy Inc.
5.0 Operation
Tfmr Overtemp appears on the LCD
and the FAULT (red) LED is on. The
PWR (green), CHG (green) and INV
(green) LED's are off.
Fatal Error $ appears on the LCD
and the FAULT (red) LED is on. The
PWR (green), CHG (green) and INV
(green) LED's are normally off.
No Inverter Comm appears on the
LCD. The FAULT (red), PWR (green),
CHG (green) and INV (green) LED's
are normally off.