3.0 Setup
SETUP: 03 Batt AmpHrs - Used to select the approximate capacity
of the battery bank connected to the inverter. This setting determines the
time the battery charger is in the Absorb Charging stage (i.e. Absorption
Time). See Table 3-1 to correlate the battery capacity to the Absorption
Time; selections are in 10 AmpHrs increments from 200 to 2500 AmpHrs.
Default setting: Batt AmpHrs= 400
Table 3-, Battery AmpHrs to Absorb Charging Time
Battery AmpHrs Selected
910 to 1100
1110 to 1300
1310 to 1500
1510 to 1700*
1710 to 1900*
1910 to 2100*
2110 to 2300*
2310 to 2500*
* these settings are active only on newer inverter revisions
SETU P
Status...
03 Batt AmpHrs
press
Status ...
Batt AmpHr = 200
Figure 3-8, SETUP: 03 Batt Amphrs Selections
Where do I set the Battery Amp-Hour setting? Select the setting based
on the 20-hour Amp-Hour (AH) capacity of your battery bank.
How do I determine my Battery Amp-Hour capacity? The inverter
requires deep cycle batteries, which are specifically made for continuous
use. Deep cycle batteries are rated either by a) amp-hours or b) reserve
capacity in minutes.
a)
Amp-hour (AH) capacity is a measurement of how many amps a battery
can deliver for a specified length of time (usually 20 hours) until the
voltage achieves 1.75 VDC / cell at 80° F.
b)
Reserve Capacity (RC) is a measure of how many minutes a battery can
deliver a certain amount of current (usually 25A) and maintain a voltage
above 1.75 VDC/cell at 80° F.
Info: If using the Reserve Capacity (25A), the 20-hour AH capacity can
be estimated by multiplying "minutes reserve capacity" by 50%.
0
200 to 300
310 to 500
510 to 700
710 to 900
rotate to
Status ...
Status...
...
Batt AmpHr= 390
Batt AmpHr = 400
Absorb Charging Time
60 minutes
90 minutes
120 minutes
150 minutes
180 minutes
210 minutes
240 minutes
270 minutes
300 minutes
330 minutes
360 minutes
390 minutes
rotate to
press to select
selection :
Status...
Batt AmpHr = 410
©2009 Magnum Energy Inc.
desired
press to save
Status...
...
Batt AmpHr = 2500