Functional Tests; Equipment Required; Power-On Check; Voltage Mode Operation Check - Xantrex XFR 6-200 Operating Manual

Xfr 1200 watt series programmable dc power supply
Hide thumbs Also See for XFR 6-200:
Table of Contents

Advertisement

Functional Tests

These functional test procedures include power-on and front panel function checks
as well as voltage and current mode operation checks.
Equipment
Required
Power-on
1. Ensure that the AC power switch is in the OFF position.
Check
2. Ensure that the output sense lines are connected in the default configuration.
3. Turn the voltage and current controls fully counter-clockwise.
4. Connect the unit to an AC outlet.
5. Turn the front panel AC power switch to ON.
After a short power-on delay, the front panel digital meters light up and the green
voltage mode LED turns on. Both voltmeter and ammeter displays read zero.
Voltage Mode
1. Ensure the voltage and current controls on the front panel are turned fully
Operation
Check
2. Connect a DVM to the output terminals on the rear panel, observing correct
3. Turn the current control a 1/2-turn clockwise. Slowly turn the voltage control
4. Compare the DVM reading with the front panel voltmeter reading to verify the
5. Turn the front panel AC power switch to OFF.
Release 3.1
Digital voltmeter (DVM) rated better than 0.5% accuracy.
DC shunt 1mV/A (±0.25%) with connecting wire. The recommended current
ratings for the DC shunt and the wire must be at least 10% more than the output
current of the power supply.
(The local sense lines are connected between terminals 1 and 2 and between
terminals 4 and 5 on the J10 sense connector as shown on the rear panel diagram
in Figure 1.2.)
counter-clockwise.
polarity.
clockwise and observe both the front panel voltmeter and the DVM.
accuracy of the internal voltmeter. Both readings should be the same. The
minimum control range is from zero to the maximum rated output for the power
supply model. The voltage mode LED turns on.
Installation
Functional Tests
43

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfr 1200 watt seriesXfr 7.5-140Xfr 12-100Xfr 20-60Xfr 35-35Xfr 40-30 ... Show all

Table of Contents