Xantrex XFR 6-200 Operating Manual page 27

Xfr 1200 watt series programmable dc power supply
Hide thumbs Also See for XFR 6-200:
Table of Contents

Advertisement

1. Minimum output voltage is <0.15% of rated voltage at zero output setting.
2. Minimum output current is <0.5% of model-rated current at zero output setting, when measured on minimum 10% of
full power load.
3. For rack mounted 6 V models, derate output current by 1.5 A per °C for operating temperatures between 30 °C and
"Environmental Specification" on page 32
50 °C. See
4. For input voltage variation over the AC input voltage range, with constant rated load.
5. For 0-100% load variation, with constant nominal line voltage.
6. Current mode noise is measured from 10% to 100% of rated output voltage, full current. For 6 V models, current
noise is measured from 2 V to 6 V, full current.
7. Maximum drift over 30 minutes with constant line, load, and temperature, after power on.
8. Maximum drift over 8 hours with constant line, load, and temperature, after 30-minute warm-up.
9. Change in output per °C change in ambient temperature, with constant line and load.
10. Typical efficiency at 100 Vac input voltage and full output power.
Release 3.1
Features and Specifications
.
Specifications
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfr 1200 watt seriesXfr 7.5-140Xfr 12-100Xfr 20-60Xfr 35-35Xfr 40-30 ... Show all