Using The Menu Options; Figure 5-3. System Meters Screen (Typical For Powerware 9315 500 480/480V Unit) - Eaton Powerware 9315 Operation Manual

300–500 kva
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

5.6 Using the Menu Options

The UPS menus allow you to display data in the information area to help you monitor and
control UPS operation. The following menus and options are available:
A
A
A
A
A
Figure 5-3 shows the LCD screen as it appears when you first start the UPS. The Meters
menu is displayed in the menu box, with the System option highlighted. In the information
area, the system meters show their current readings.
System Normal
Alarm:
Notice: None
Meters

Figure 5-3. System Meters Screen (Typical for Powerware 9315 500 480/480V Unit)

The Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the kVA, KW, and power factor measurements. The output
area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area
displays the DC voltage (V) and the DC current (I).
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
EATON Powerware
®
Meters − Displays UPS performance meters for the system or critical load.
Events − Displays the list of Active System Events and a historical log of system events.
Statistics − Displays statistical information about UPS operations for the battery, load, or
line.
Graphics − Displays a real-time graphic representation of the flow of current through
the internal UPS components.
Setup − Allows you to configure the UPS communication port and set the date and time
for the timestamp.
None
Battery
Percent
100%
VAB
482
Meters
System
Load Amps
Events Statistics Graphics Setup
Uninterruptible Power System
Input
VBC
VCA
FREQ
484
481
60.0
IA
IB
IC
515
512
520
KVA
KW
PF
433
416
0.96
Bypass
VAB
VBC
VCA
482
484
481
Using the Monitor Panel
04 NOV 1997
14:23:45
Output
VAB
VBC
VCA
FREQ
480
480
480
60.0
IA
IB
IC
IN
475
473
476
000
KVA
KW
PF
394
392
0.99
Battery
V
I
540
000
5−5