Resetting The Ups System After Load Off; To Place The Ups In Normal Mode - Eaton Powerware 9315 Operation Manual

300–500 kva
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

Starting and Stopping the UPS
The following describes the switches on the Control Panel (see Figure 4-1):
A
The MODE switch is a two-position rotary switch that controls the manual transfer of the
UPS to and from Bypass mode. The MODE switch is used to:
− Place the critical load in Bypass mode when the UPS is operating in Normal mode and
− Prevent transfer to Normal mode when the UPS is in Bypass mode.
− Shut down the power processing unit (inverter and rectifier) of the UPS.
A
The BATTERY switch is a two-position rotary switch that allows you to manually shunt
trip the battery breakers in remote cabinets.
A
The circuit breaker (CB1) switch controls the operation of the rectifier and inverter. If
CB1 is on (closed), the rectifier turns on when the START switch is activated and the
proper voltage is at the input terminals.
A
The PUSH TO RESET button is described in Resetting the UPS System after Load Off" on
page 12−2.
A
The START switch activates the power controls on the Control Panel. The START switch
is center-biased (the key will rest only in the upright position). Its operation is similar to
that of an automobile ignition switch. After setting the operator controls, you turn the
START switch to the right momentarily to activate the controls. When you release it, it
returns to the upright position.
The following sections describe how to operate these controls to start, stop, or change the
operating mode of the UPS.

4.1.1 To Place the UPS in Normal Mode

1. Close Input Power Feeder breaker
2. Verify that the Load Off PUSH TO RESET button is pressed in.
3. Turn the BATTERY switch to NORMAL.
4. Turn the MODE switch to NORMAL.
5. Move the CB1 switch to ON.
6. Turn the START switch to the right momentarily.
7. Close battery breaker(s).
4−2
EATON Powerware
the bypass source is within acceptable limits. If the transfer does not occur within two
seconds, an alarm sounds.
The rectifier turns on, then the inverter turns on. The UPS display and alarm alert
you to close the battery breaker.
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
®