Emergency Load Off; Automatic Battery Charge Current Limit; Installation Features; Options And Accessories - Eaton Powerware 9315 Operation Manual

300–500 kva
Hide thumbs Also See for Powerware 9315:
Table of Contents

Advertisement

2.4.5 Emergency Load Off

A LOAD OFF button is provided for situations where you must immediately remove all
power to your critical load. The button is located on the front of the UPS for quick access
and is covered with a clear plastic shield to prevent inadvertent operation. The shield must
be raised before pressing the button. The LOAD OFF button is described in detail in
Chapter 12, Using the LOAD OFF Button."

2.4.6 Automatic Battery Charge Current Limit

A preset limit restricts battery charging current to protect batteries from damage due to
high current charging. Charging at high currents can overheat and damage batteries.

2.4.7 Installation Features

Power wiring can be routed through the top or bottom of each UPS cabinet. External
sensing and monitoring control wire must be installed in accordance with Class 2 wiring
methods. Bottom entry is provided for Class 2 wiring.

2.5 Options and Accessories

Contact your sales representative for information about any of these available options:
2.5.1 Battery
You can enhance the protection provided by your UPS with one or more backup battery
supplies equipped with sealed lead-acid, maintenance-free batteries in a matching cabinet.
Each battery cabinet contains individual modular battery trays and a battery circuit breaker.
Several battery capacities are available.
The UPS battery cabinets can be paralleled; you can increase your battery backup time by
adding battery cabinets to your UPS system. The Powerware 9315 can support up to four
battery cabinets.

2.5.2 External Battery Disconnect

An optional DC circuit breaker, enclosed in a wall-mounted box adjacent to the UPS,
provides a manual means of disconnecting a battery that is located remotely from the UPS.
This option is described further in Chapter 6, Using Features and Options."

2.5.3 Power Distribution Module (LV models only)

An optional output Power Distribution Module (PDM) is available to distribute the output
power of the UPS to your critical load. The PDM cabinet has one or two panels, each
containing up to 42 poles for breaker switches, provides flexibility for the needs of your
facility. Each panel is controlled by one 225A feeder breaker. The PDM is enclosed in a
separate cabinet that matches the UPS. This option requires a 480 to 208V transformer.
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
EATON Powerware
®
Getting Started
2−5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents