Configuration
Function
Prompt
Lower Display
Output Rate Down Value
PCT/M DN
OUTHiLIM
High Output Limit
OUTLoLIM
Low Output Limit
High Reset Limit
I Hi LIM
Low Reset Limit
I Lo LIM
Controller Dropoff Value
DROPOFF
Output Relay Deadband
DEADBAND
OUT HYST
Output Relay Hysteresis
Failsafe Mode
FAILMODE
Failsafe Output Value for
FAILSAFE
all outputs except 3P Step
Failsafe Output Value for
3P Step
SW FAIL
PDMR/ Position
Proportional Motor Position
when Slidewire Fails
Power-up Preset Output
MAN OUT
for Manual Output
Power-up Preset Output
AUTO OUT
for Automatic Output
PBorGAIN
Proportional Band or Gain
Units
MINorRPM
Reset Units
32
Function
Name
UDC3300 Basic Model: DC330B User Manual
Selections or
Range of Setting
Upper Display
0 to 9999% per minute
–5.0 to 105% of output
–5.0 to 105% of output
Within the range of output limits
Within the range of output limits
–5 to 105% of output
Time Duplex:
–5.0 to 25.0%
On/Off Duplex:
0.0 to 25.0%
Position Prop. and 3P Step:
0.5 to 5.0%
0.0 to 100.0% of PV Span for
On/Off control.
NO LAT
LATCH
Set within the range of the
output limits. 0 to 100%
0 PCT (motor goes to closed
position)
100PCT (motor goes to open
position)
0 PCT (motor goes to closed
position)
100PCT (motor goes to open
position)
Within the range of output limits
Within the range of output limits
PB PCT
GAIN
RPM
MIN
Factory
Setting
0
100
0.0
100.0
0.0
0
1.0
0.5
NO LAT
0.0
- -
- -
- -
- -
GAIN
MIN
5/00