Function No.
Parameter
Function name
and range
Mass to be
Fnc09
compared with
1 to 2
near-zero
Fnc10
Set value of
-99999 to 99999
upper limit
Fnc11
Set value of
-99999 to 99999
lower limit
Mass to be
Fnc12
compared with
upper and
1 to 2
lower limit
Output logic of
Fnc13
upper and
1 to 2
lower limit
5.4.4.

The List Of The Hold Function

Function No.
Parameter
Function name
and range
HLd01
Averaging time
0.00 to 9.99
HLd02
Start wait time
0.00 to 9.99
HLd03
Condition of
0 to 2
automatic start
Release due to
HLd04
falling control
0 to 1
HLd05
Time release
0.00 to 9.99
Release due to
HLd06
0 to 99999
fluctuation
HLd07
Release in
0 to 1
near-zero range
This hold function only works when
This hold function has no function when
HLd01
(averaging time) works only when
AD-4430B
Item to be compared with near-zero.
1 : Gross weight
2 : Net weight
Reference value for the upper limit.
Decimal point position is linked to CAL02.
Reference value for the lower limit.
Decimal point position is linked to CAL02.
Item to be compared with the upper and lower limit.
1 : Gross weight
2 : Net weight
Logic used when the result of the comparison with
the upper and lower limit is output
1 : Positive logic
2 : Negative logic
Time to perform the averaging. Unit : second.
0.00 is not averaged.
Time to wait before commencing hold or averaging.
Unit : second.
Condition to start the hold or averaging automatically.
0 : Do not use automatic start.
1 : Above the near-zero range, and stable.
2 : Above the near-zero range.
Release when control input is falling.
0 : Do not release
input
1 : Release
Release after a set amount of time has passed.
Unit : second. 0.00 is not averaged.
Release when fluctuation from the holding value
range of
exceeds a set value. The decimal point position is the
same as the setting of CAL02.
Release when the weighing value is in the near-zero
range.
0 : Do not release.
1 : Release.
Fnc07
Description
Description
(hold) is set to 2 (peak hold) or 3 (averaging hold).
Fnc07
(hold) is set to 1 (normal hold).
Fnc07
(hold) is set to 3 (averaging hold).
- 33 -
Default
value
1
10
-10
1
1
Default
value
0.00
0.00
0
1
0.00
0
0