Magnum 6K8-Series Industrial Field Switch
NOTE: for Power Substations: In support of the IEEE 1613 Class 2 standard, GCI
advises that, for substation applications, the RJ-45 ports are intended for connectivity to
other communication equipment such as routers or telecommunication multiplexers
installed in close proximity (i.e., less than 2 meters or 6.5ft) to the 6K8. It is not
recommended to use these ports in substation applications to interface to field devices
across distances which could produce kigh (greater than 2500V ) levels of ground
potential rise (GPR) during line-to-ground fault conditions. The 6K8 passes the
1613specifications for zero packet loss with fiber ports & with RJ45 ports used as
indicated here.
3.2.5
Connecting Twisted Pair (CAT5E or better, Unshielded or
Shielded)
The RJ-45 Gigabit ports of the Magnum 6K8-Series can be connected to the
media types, 1000BASE-T or CAT 5E or better 100-ohm UTP or shielded twisted pair
(STP) balanced cable. The CAT 5E or better 100-ohm UTP or shielded twisted pair
(STP) balanced cable is recommended to use when making 1000BASE-TX connections.
In either case, the max distance for unshielded twisted pair cabling is 100 meters (328 ft).
Media
Twisted Pair (CAT 5E)
NOTE : It is recommended that high quality CAT. 5E cables (which work for both 100
Mb and 1000Mb) be used whenever possible in order to provide flexibility in a
mixed-speed network.
The following procedure describes how to connect a 1000BASE-T twisted pair segment
to the RJ-45 port. The procedure is the same for both unshielded and shielded twisted
pair cables.
1.
1000Base-T connections require that all four pairs or wires be connected. Insert
either end of the cable with an RJ-45 plug into the RJ-45 connector of the port.
Note that, even though the connector is shielded, either unshielded or shielded
cables and wiring may be used.
2.
Connect the other end of the cable to the
corresponding device
3.
Use the LINK LED to ensure proper connectivity by
noting that the LED will be illuminated when the unit
is powered and proper connection is established
3.2.6

Connecting Gigabit Media Using GBICs

The Gigabit ports accept industry-standard GBICs for
www GarrettCom com
.
.
Installation and User Guide (04/07)
IEEE Standard
1000BASE-T
29
Connector
RJ-45