Magnum 6K8-Series Industrial Field Switch
C5.1 UL Requirements
The following must be adhered to in order to conform to UL requirements:
1.
Minimum 18 AWG cable for connection to a Centralized DC power source.
2.
Minimum 14 AWG cable for connection to earthing wiring.
3.
Use only with Listed 10 A circuit breaker provided in building installation.
4.
"Complies with FDA radiation performance standards, 21 CFR subchapter J."
or equivalent.
5.
Fastening torque of the lugs on the terminal block: 9-inch pound max.
6.
Centralized DC Power Source cable securement, use at least four Minimum 14
AWG cable ties to secure the cable to the rack at least 4 inches apart with the
first one located within 6 inches of the terminal block.
C6.0
ORDERING INFORMATION (Optional)
To order the optional Dual-Source -48VDC power supply factory installed,
order "Dual-Src48V" as a separate line item following the product model.
Example: Magnum 6K8 -48VDC
Similarly, order the "Dual –source 24VDC" or "Dual-source 125VDC" as a
separate line item following the product model.
Example: Magnum 6K8 -24VDC
C7.0
OPERATION
Operation of the Dual-Source Magnum 6Ks-48VDC, 24VDC and 125VDC
Switch models are identical to that of the standard models.