17. PANEL SPECIFICATIONS

17.1 ENCLOSURE SPECIFICATIONS

DESCRIPTION
ENCLOSURE SIZE
TOP CABLE ENTRIES
BOTTOM CABLE ENTRIES
REAR CABLE ENTRIES

17.2 ELECTRICAL SPECIFICATIONS

ELECTRICAL DESCRIPTION
MAINS VOLTAGE
BATTERY VOLTAGE
SYSTEM VOLTAGE
SYSTEM VOLTAGE RIPPLE
CHARGER SIZE
ZONE VOLTAGE
SOUNDER ALARM OUTPUTS
AUXILIARY FAULT OUTPUT
AUXILIARY FIRE OUTPUT
NUMBER OF LOOPS
MAXIMUM NUMBER OF ZONES
MAXIMUM LOOP CAPACITY
MAXIMUM ZONE CAPACITY
MAXIMUM LOOP RESISTANCE
MAXIMUM LOOP CAPACITANCE
MAXIMUM VOLTAGE PICKUP ALLOWED
REMOTE SOUNDER ACTIVATION
SOUNDER END OF LINE DEVICE
CHARGER VOLTAGE
LOOP SHORT CIRCUIT PROTECTION
CHARGER SHORT CIRCUIT PROTECTION
TOTAL CHARGER OUTPUT
Approved Document No: GLT.MAN-105A
Issue : 2.02
Authorised: GH
VALUE
480 x 395 x 100 mm
20 x 19mm DIA GROMMETED ENTRIES
10 x 19mm KNOCKOUT ENTRIES
2 SNAP OUTS, 60 x 20mm
VALUE
230V AC +/- 10% @ 50/60 Hz
24V DC (2 X 12V SLA BATTERY)
24V DC NOMINAL (18 – 32 V)
2V PK-PK MAX
UP TO 7AH in 24 Hours
24V DC NOMINAL (+9 volt data)
4 x 250mA @ 24V DC (Nominal)
1 x RELAY SELV (1A MAX)
1 x RELAY SELV (1A MAX)
2 LOOPS
16 ZONES
126 DEVICES PER LOOP
16 DEVICES PER ZONE
25 ohms
0.3μF
50mV
VIA N/O CONTACTS
10 K RESISTOR
28.3V @ 22-24
750mA
Batteries less than 20V
1.5 Amp
Date: 16/07/2007
Software:PANEL:R1107 & LOOP:R1062
o
C (NO BATTERY CONNECTED)