Panel Specifications; Enclosure Specifications; Electrical Specifications - Zeta SP-64,126 Installation Manual

64 or 126 device capacity, single loop analogue addresable fire alarm control panel
Table of Contents

Advertisement

SIMPLICITY INSTALLATION MANUAL.

17. PANEL SPECIFICATIONS

17.1 ENCLOSURE SPECIFICATIONS

DESCRIPTION
ENCLOSURE SIZE
TOP CABLE ENTRIES
BOTTOM CABLE ENTRIES
REAR CABLE ENTRIES

17.2 ELECTRICAL SPECIFICATIONS

ELECTRICAL DESCRIPTION
MAINS VOLTAGE
BATTERY VOLTAGE
SYSTEM VOLTAGE
SYSTEM VOLTAGE RIPPLE
CHARGER SIZE
LOOP VOLTAGE
SOUNDER ALARM OUTPUTS
AUXILIARY FAULT OUTPUT
AUXILIARY FIRE OUTPUT
NUMBER OF LOOPS
MAXIMUM NUMBER OF ZONES
MAXIMUM LOOP CAPACITY
MAXIMUM ZONE CAPACITY
MAXIMUM LOOP RESISTANCE
MAXIMUM LOOP CAPACITANCE
MAXIMUM VOLTAGE PICKUP ALLOWED
REMOTE SOUNDER ACTIVATION
CHARGER VOLTAGE
LOOP SHORT CIRCUIT PROTECTION
CHARGER SHORT CIRCUIT PROTECTION
TOTAL CHARGER OUTPUT
Approved Document No: GLT.MAN-107
Issue : 2.00
Authorised: GH
VALUE
355 x 275 x 100 mm
12 x 19mm DIA GROMMETED ENTRIES
2 x 19mm KNOCKOUT ENTRIES
2 SNAP OUTS, 60 x 20mm
VALUE
230V AC +/- 10% @ 50/60 Hz
24V DC (2 X 12V SLA BATTERY)
24V DC NOMINAL (18 – 32 V)
2V PK-PK MAX
UP TO 7AH in 24 Hours
24V DC NOMINAL (+9 volt data)
LOOP POWERED SOUNDERS ONLY
24V RELAY DRIVE SIGNAL (NORMALLY ON)
24V RELAY DRIVE SIGNAL
1 LOOP
8 ZONES (4 FOR SIMPLICITY 64)
126 DEVICES (64 FOR SIMPLICITY 64)
16 DEVICES PER ZONE
25 ohms
0.3μF
50mV
VIA N/O CONTACTS
28.3V @ 22-24
750mA
Batteries less than 20V
1.1 Amp
Date: 4/06/2007
Software:PANEL:R1107 & LOOP:R1062
o
C (NO BATTERY CONNECTED)
PAGE 31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simplicity plus

Table of Contents