7.5 ADDRESS - ZONE TABLE

On the Premier AD, each available address corresponds to a zone, with 1-16 being in zone 1,
17-32 being in zone 2, 33-48 in zone 3 etc.
The table below shows the dip switch settings for each address, and the zone that address will
be in.
SW 4,3,2,1
OOOO OOO1 OO1O OO11 O1OO O1O1 O11O O111 1OOO 1OO1 1O1O 1O11 11OO 11O1 111O 1111
SW
OOO
N/A
1
7,6,5 OO1
16
17
O1O
32
33
O11
48
49
1OO
64
65
1O1
80
81
11O
96
97
111
112
113
114
Eg to set address 37, find 37 in the table. It is at sw 7,6,5 = 010, and sw 4,3,2,1= 0101
Remembering that 0 = ON & 1 = OFF, the switch settings for 37 are:
7=ON, 6=OFF, 5=ON, 4=ON, 3=OFF, 2=ON, 1=OFF
As an alternative to using this chart, use the table on the following page:-
Approved Document No: GLT.MAN-105A
Issue : 2.02
Authorised: GH
2
3
4
5
6
18
19
20
21
22
34
35
36
37
38
50
51
52
53
54
66
67
68
69
70
82
83
84
85
86
98
99
100
101
102
115
116
117
118
Date: 16/07/2007
7
8
9
10
11
23
24
25
26
27
39
40
41
42
43
55
56
57
58
59
71
72
73
74
75
87
88
89
90
91
103
104
105
106
107
119
120
121
122
123
Software:PANEL:R1107 & LOOP:R1062
LOOP 1
12
13
14
15
ZONE 1
28
29
30
31
ZONE 2
44
45
46
47
ZONE 3
60
61
62
63
ZONE 4
76
77
78
79
ZONE 5
92
93
94
95
ZONE 6
108
109
110
111
ZONE 7
124
125
126
N/A
ZONE 8
PAGE 13
LOOP 2
ZONE 9
ZONE 10
ZONE 11
ZONE 12
ZONE 13
ZONE 14
ZONE 15
ZONE 16