12.5 VIEWING DEVICE STATUS

On the Premier AD, all loop devices can be viewed from Configuration Menu 1, or
viewed & edited from Configuration Menu 2.
Enter configuration menu 2 as described above, and select option 5 (Edit Device)
The following screen is shown
The screen is divided into the following sections:-
Configured Device Type
This shows the Device that was at this address during
the last loop configuration.
There are 8 possibilities for this:-
Optical, Ion, Heat, Call-Pt, Sounder, I/O Unit,
Zone Mon or CO
Analogue Value
This shows the analogue value that the device is sending
To the panel. For detectors, this value is usually about 25
for clean air, and 55 during alarm. Non analogue devices
such as call points and I/O units have a normal value of 16,
and an alarm value of 64. They will return a value of less
than 8 to report a fault condition.
Device Status
This is the current status of the device. It will show one of
the following values:-
Normal, Fault, Alarm or Prealarm
Fault Description
If the device is in a fault condition, a description of the
fault will appear here. It will show one of the following
messages:-
FAULT
MEANING
Changed
The device had been changed with one of a different type since last
configuration. The message will flash between Changed, and the new
type of device seen (eg. Ion).
Missing
The device is not communicating (ie removed , damaged or Address
setting changed)
Side A Only
There is a break in the cable, and the device is only seen from Side A
Side B Only
There is a break in the cable, and the device is only seen from Side B
2-ADDR
Two devices have the same address setting
No message
This device is signalling an internal fault by returning a value of less than
8. (EG sounder control unit that has lost it`s power supply.)
Device Label
This is the 20 character description of the device location
entered by the installer. To change this Press Enter button
to activate the cursor.
Approved Document No: GLT.MAN-105A
Issue : 2.02
Authorised: GH
Date: 16/07/2007
Software:PANEL:R1107 & LOOP:R1062
Optical
Analog:
25
Normal
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
Optical
Analog:
25
Normal
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
Optical
Normal
Analog:
25
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
Optical
Analog:
25
Normal
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
Optical
Changed
Analog:
25
Fault
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
Optical
Analog:
25
Normal
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
PAGE 20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Premier ad

Table of Contents