Zeta ID2/2 User Manual

Intelligent 2 wire fire detection system with ‘id’ technology
Hide thumbs Also See for ID2/2:

Advertisement

Quick Links

INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624
INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH
'ID' TECHNOLOGY
USER MANUAL, MAINTENANCE
GUIDE & LOG BOOK
PAGE 0
Approved Document No: GLT2-211-7-2
Issue 1.00
Author: NRPJ
Date: 23/1/2013

Advertisement

Table of Contents
loading

Summary of Contents for Zeta ID2/2

  • Page 1 INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH ‘ID’ TECHNOLOGY USER MANUAL, MAINTENANCE GUIDE & LOG BOOK PAGE 0 Approved Document No: GLT2-211-7-2 Issue 1.00 Author: NRPJ Date: 23/1/2013...
  • Page 2: Table Of Contents

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 TABLE OF CONTENTS WHAT TO DO IF THE FIRE ALARM PANEL SHOWS AN ALARM (RED LED) ..........2 WHAT TO DO IF THE FIRE ALARM PANEL SHOWS A FAULT (YELLOW LED) ..........2 1.
  • Page 3: What To Do If The Fire Alarm Panel Shows An Alarm (Red Led)

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 WHAT TO DO IF THE FIRE ALARM PANEL SHOWS AN ALARM (RED LED) Write down the LCD reading and which LEDs are lit (either in the log book, or on a piece of paper for transferring to the log book later) Follow the building procedures for fire alarm activation.
  • Page 4: Fire Alarm Control Panel Safety Issues

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 1. FIRE ALARM CONTROL PANEL SAFETY ISSUES NOTE: When the Simplicity Plus panel is operating normally, i.e. not being tended by service personnel, the access door must be closed and locked.
  • Page 5: User Responsibilities & Maintainence Of The Fire Alarm System, Including The Facp & Its Integral Pse

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, INCLUDING THE FACP & ITS INTEGRAL PSE According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings (BS5839: Pt 1: 2002), the owner or person having control of the premises should appoint a responsible person to oversee the effective operation of the Fire Alarm System (Clause 47.1).
  • Page 6: Panel Indications & Controls

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 4. PANEL INDICATIONS & CONTROLS 4.1 PANEL INDICATIONS The Infinity ID2 has been designed to be as straight forward as possible. To help achieve this it has been designed so that its LCD screen is the primary display.
  • Page 7: Checking The Panels Indication Leds

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 This access level is obtained by entering the user access code 123 . Here the user can start or stop the external sounders, silence the panel’s internal buzzer, or reset the panel.
  • Page 8: The Fire Condition

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 5. THE FIRE CONDITION 5.1 HOW THE SIMPLICITY INDICATES AN ALARM When the Infinity ID2 Fire Alarm Panel is set into alarm by a Detector or Manual Call Point located in a zone that is not already in alarm it will: - ...
  • Page 9: The Fault Condition

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 6. THE FAULT CONDITION 6.1 DIFFERENT TYPES OF FAULT The fire alarm monitors itself, and any equipment connected to it, for any faults that can occur. If a fault occurs, the Panel responds by activating its Internal buzzer and lighting the General Fault light and displaying the fault information on its LCD display.
  • Page 10: What To Do If A Fault Condition Occurs

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 6.2 WHAT TO DO IF A FAULT CONDITION OCCURS If a fault occurs, the responsible person should:  Enter access code 123 to enable controls and press silence buzzer button to silence the fault buzzer. ...
  • Page 11: Other Led Indications

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 6.3 OTHER LED INDICATIONS DISABLEMENTS TEST MODE PAGE 10 Approved Document No: GLT2-211-7-2 Issue 1.00 Author: NRPJ Date: 23/1/2013...
  • Page 12: Disablements

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 7. DISABLEMENTS 7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For example, if there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is possible for the user to disable that zone during the risk period and then enable it again afterwards.
  • Page 13: System Description

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 8. SYSTEM DESCRIPTION FIRE ALARM SYSTEM SUMMARY FIRE ZONE INFORMATION ZONE DESCRIPTION ZONE NO. QTY SNDR QTY MCP QTY HEADS A brief description of all the rooms and areas contained in each zone. SOUNDER CIRCUIT INFORMATION SOUNDER SOUNDER CIRCUIT DESCRIPTION...
  • Page 14 INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 DETAILED ZONE CONTENTS This must be fully recorded by an authorised Engineer before system handover. Description Description Description Zone 1 Zone 2 Zone 3 Zone 4 Zone 5...
  • Page 15: Fire Alarm Log Book

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 9. FIRE ALARM LOG BOOK It is recommended that this LOG BOOK section of the Manual be maintained by the responsible person(s) on site, who should ensure every event is properly recorded (including fire alarm conditions, failures, tests, temporary disconnections, disablements, enablements, dates of installing engineers’...
  • Page 16: Maintenance Work

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 MAINTENANCE WORK LOOP & ZONE/ ADDITIONAL WORK DATE TIME REASON FOR WORK WORK CARRIED OUT SIGNED ADDRESS LOCATION REQUIRED PAGE 15 Approved Document No: GLT2-211-7-2 Issue 1.00 Author: NRPJ Date: 23/1/2013...
  • Page 17 INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 MAINTENANCE WORK (CONTINUED) LOOP & ZONE/ ADDITIONAL WORK DATE TIME REASON FOR WORK WORK CARRIED OUT SIGNED ADDRESS LOCATION REQUIRED PAGE 16 Approved Document No: GLT2-211-7-2 Issue 1.00 Author: NRPJ...
  • Page 18 INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 UNWANTED (FALSE) ALARMS CAUSE (IF MAINTENANCE FURTHER LOOP & ZONE/ KNOWN) OR MAINTENAN CATEGORY OF DATE TIME VISIT NEEDED ACTION SIGNED ADDRESS LOCATION ACTIVITIES IN CE FINDINGS...
  • Page 19 INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 UNWANTED (FALSE) ALARMS (CONTINUED) CAUSE (IF MAINTENANCE FURTHER LOOP & ZONE/ KNOWN) OR MAINTENAN CATEGORY OF DATE TIME VISIT NEEDED ACTION SIGNED ADDRESS LOCATION ACTIVITIES IN...
  • Page 20 INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DETAILS OF EVENT LOOP & ZONE/ DATE DATE TIME (INCLUDING CAUSE IF ACTION REQUIRED INITIALS ADDRESS LOCATION...
  • Page 21: All Events Other Than Maintenance Work Or False Alarms (Continued)

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS (CONTINUED) DETAILS OF EVENT LOOP & ZONE/ DATE DATE TIME (INCLUDING CAUSE IF ACTION REQUIRED INITIALS ADDRESS...
  • Page 22: Commissioning The System, Including Power Supply Equipment P.s.e

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 10. COMMISSIONING THE SYSTEM, INCLUDING POWER SUPPLY EQUIPMENT P.S.E.  The commissioning of this fire alarm system should be performed by a qualified commissioning engineer, who has an understanding of sections 2, 3, &...
  • Page 23: Design Certificate

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 Design Certificate (Page 1 of 2) Certificate of DESIGN for the Infinity ID2 Fire Alarm System installed at: ADDRESS: I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the design of the fire alarm system, particulars of which are set out below, CERTIFY that the said design for which I/we have been responsible complies to the best of my/our knowledge and belief with the recommendations of section 2 of BS 5839-1:2002 for the system category described below, except for the variations, if any,...
  • Page 24 INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 Design Certificate (Page 2 of 2) Measures incorporated to limit false alarms. Account has to be taken of the guidance contained in section 3 of BS 5839-1: 2002 and, more specifically (tick as appropriate): The System is manual.
  • Page 25: Installation Certificate

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 Installation Certificate Certificate of INSTALLATION for the Infinity ID2 Fire Alarm System installed at: ADDRESS: I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the installation of the fire alarm system, particulars of which are set out below, CERTIFY that the said installation for which I/we have been responsible complies to the best of my/our knowledge and belief with the specifications described below, and with the recommendations of BS5839-1:2002, except for the...
  • Page 26: Commissioning Certificate

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 Commissioning Certificate Certificate of COMMISSIONING for the Infinity ID2 Fire Alarm System installed at: ADDRESS: I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the commissioning of the fire alarm system, particulars of which are set out below, CERTIFY that the said work for which I/we have been responsible complies to the best of my/our knowledge and belief with the recommendations of Clause 39 of BS5839-1:2002, except for the variations, if any, stated in this certificate...
  • Page 27: Acceptance Certificate

    INFINITY ID2 USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Software Versions: PANEL 0.X – R8629 & LOOP 0.J-R624 Acceptance Certificate Certificate of ACCEPTANCE for the Infinity ID2 Fire Alarm System installed at: ADDRESS: I/we being the competent person(s) responsible (as indicated by my/our signatures below) for the acceptance of the fire alarm system, particulars of which are set out below, ACCEPT the system on behalf Name ( Position:...