Locate Or Verify A Device; Using The Event Log - Zeta NPAD 2 Installation Manual

Analogue addressable fire alarm control panel
Table of Contents

Advertisement

PREMIER AD INSTALLATION MANUAL.
Device Identification
This is the Zone, Loop and address of the device. This is
how the device will probably be referred to on the
system drawings.

12.6 LOCATE OR VERIFY A DEVICE

From the edit device screen, it is possible to send commands to individual devices to start their
sounder, or to turn on their alarm LED.
Select the loop and address for the device to be checked.
If the device is a detector, its LED can be turned on by pressing the
TEST SELECT Button. An star will appear in the top right hand corner
to show that the LED has been lit on this device. Press again to turn off.
If the device is an addressable sounder, or a detector with a sounder
base attached, the sounder can be started by pressing the
TEST button. The Outline sounder Symbol turns solid to show that the
Sounder is active. Press again to turn off.
The LED & sounder can both be activated if required.
Scrolling to another device or exiting the menu will automatically turn the LED or sounder off.

12.7 USING THE EVENT LOG

The Premier AD has a 2048 entry event log. In the event of the log
being full, it will wrap around, and overwrite the earliest entries.
The event log can be viewed through Configuration Menu 1 by
selecting Option 3 - View Event Log. The screen prompts for which
events to display: Alarms, Faults, System or All.
Alarms
If the alarm option is shown, only alarms will be displayed. The screen
will show the event number, the date, the time, the type of event (in
this case, a DEVICE ALARM), and the Zone, loop and address,
if appropriate. Next & Previous buttons will cycle through the list.
Faults
Selecting this option will display all the faults recorded on the system,
Both device faults and general faults. The screen will show the event
number, the date, the time, the type of event (in this case, a
DEVICE CHANGED fault), and the Zone, loop and address,
if appropriate. Next & Previous buttons will cycle through the list.
System.
The Premier AD also records other non critical items, such as
keyswitch turned on etc. These can be used to help determine the
chain of actions before or after an event.
The type of events recorded are:- Power On/Startup, Panel Reset,
Evacuate, Keyswitch ON, Keyswitch OFF, Sounders Silenced,
Configure Loops, Time & Date Set, Zone Disabled, Zone Enabled, Device Disabled, Device Enabled,
Zone Test Start, and Zone Test Finish.
Note: during installation and commissioning, it is possible to create a large number of events,
especially if a configured loop is disconnected. This is normal, and is not a case for concern. These
events can be cleared, using Configuration Menu 2.
To clear the event log, go to Configuration Menu 2 and select
option 6 (Configure System). Select Option 3 to clear the event log.
Approved Document No: GLT.MAN-105A
Issue : 2.02
Authorised: GH
Date: 16/07/2007
Software:PANEL:R1107 & LOOP:R1062
Optical
Analog:
25
Normal
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
Optical
Analog:
25
Normal
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
Optical
Analog:
25
Normal
Fl 3 Bedroom 303
Zone:01
Lp:1 Ad:016
View Event Log
1: Alarms
4: All
2: Faults
3: System
Event 167
13-01-2007 17:21
Device Alarm
Zone:03
Lp:1 Ad:037
Event 173
25-01-2007 17:21
Device Changed
Zone:01
Lp:1 Ad:013
Event 174
25-01-2007 17:22
Keyswitch On
System Menu
1: Set Clock
2: Version Info
3: Clear Logs
*
PAGE 21